Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
CAGE Information
Code | Company |
---|---|
02964 | AMERICAN STERILIZER COMPANY DBA AMSC |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION AND 1000.0 DC SINGLE LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 SINGLE LOCATION |
TTQY | TERMINAL TYPE AND QUANTITY | 4 QUICK DISCONNECT, MALE |
AAQL | BODY STYLE | SINGLE POLE TYPE |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC SINGLE LOCATION AND 65.0 DC SINGLE LOCATION |
AGAV | END ITEM IDENTIFICATION | 6530-01-147-9531 |
ADAT | BODY WIDTH | 0.750 INCHES NOMINAL |
ADAQ | BODY LENGTH | 2.000 INCHES NOMINAL |
ZZZP | PURCHASE DESCRIPTION IDENTIFICATION | 02964-P84386-001 |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
PKWT | UNPACKAGED UNIT WEIGHT | 0.140 POUNDS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATION |
ADTV | CASE MATERIAL | PLASTIC |
AKPX | POLE QUANTITY | 1 |
CPRQ | RESET METHOD | MANUAL |
CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 0.004 NOMINAL SINGLE LOCATION |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 PUSH BUTTON |
FREQ | FREQUENCY IN HERTZ | 50.0 FIRST LOCATION |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
THSD | THREAD SERIES DESIGNATOR | UNC |
CBME | CUBIC MEASURE | 0.031 CUBIC FEET |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.750 INCHES NOMINAL AND 1.562 INCHES NOMINAL |
CPRX | ACTUATOR POSITION DESIGNATION | AS |
CQJX | NOMINAL THREAD SIZE | 0.109 INCHES |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC SINGLE LOCATION AND 30.0 AMPERES DC SINGLE LOCATION |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
FREQ | FREQUENCY IN HERTZ | 400.0 SECOND LOCATION |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.660 INCHES NOMINAL |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | RELAY TRIP SINGLE LOCATION |
FEAT | SPECIAL FEATURES | ACTUATOR IS WHITE PLASTIC WITH ON-OFF IN BLACK 0.125 INCH LETTERING HOT STAMPED ON FACE,O/A DIM. 0.750 IN. WIDE,1.185 IN. LONG |