Follow Us on Google+

Request A Price Quote:

Part Number

Part Number:
NSN:
NIIN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

CAGE Information

Code Company
79500 WESTINGHOUSE ELECTRIC CORP

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 225.0 AMPERES AC ALL LOCATIONS AND 225.0 AMPERES DC ALL LOCATIONS
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 225.0 AMPERES AC ALL LOCATIONS AND 225.0 AMPERES DC ALL LOCATIONS
AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 UNTHREADED HOLE
FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 200.0 ALL LOCATIONS
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 500.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS
AKPX POLE QUANTITY 3
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
AEBV UNTHREADED MOUNTING HOLE DIAMETER 0.375 INCHES NOMINAL
ADTV CASE MATERIAL PLASTIC
CPRQ RESET METHOD MANUAL
CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS
CPRW ACTUATOR FUNCTION TRIP W/SEPARATE RESET
CPRJ TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS
CRCF TRIP RELEASE AMBIENT TEMP RATING 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 5400.000 NOMINAL AT 150 PCT ALL LOCATIONS
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 20000.0 AC ALL LOCATIONS AND 15000.0 DC ALL LOCATIONS

Similar Parts

S05Y8689 , S05Y8689 , 5925-00-259-7485 , 5925002597485 , 002597485